Radiation Resistance Up to 100x106 cJ/kg (up
to 100 Mrad)
Approvals
Cable
Construction
Bare copper, fine wire conductors
to DIN VDE 0295 cl. 5, BS 6360
cl. 5 and IEC 60228 cl. 5
Conductor insulation of halogen-free
compound TI6, to E DIN VDE 0281
part 14
Color coded to DIN VDE 0293-308
Green-yellow grounding in
the outer layer
Conductors laid up in layers with
optimal lay-length
Separating layer
Shield braid of tinned copper
wires, coverage approx. 85%
Halogen-free jacket compound
TM7, to E DIN VDE 0281 part 14
Jacket color: Gray (RAL 7001)
LS0H = Low Smoke
Zero Halogen-Free
Application
Halogen-free,
flame retardant control cables
are used for instrumentation and
control cables in tooling machinery,
conveyor and transportation belts,
production lines, in plant construction,
air-conditioning systems as well
as in iron and steel works. For
fixed installation or for flexing
applications, for casual, not constantly
recurring free movement without
forced motion and without tensile
stress for medium mechanical loads.
The cable is suitable for use in
dry, damp and wet environments
for installation above, on, in
and beneath plaster as well as
in masonry and concrete walls except
for direct embedding in vibrated,
compacted or tamped concrete, not
suitable for imbedding in solidified
or compressed concrete.
An interference-free transmission
of signals and pulse in assured by
the high degree of shielding. EMI = Electromagnetic
Interference
To optimize the EMI features we recommend
a large round contact of the copper
braiding on both ends.
=
The product
is conformed
with
the EC
Low-Voltage
Directive
73/23/EEC
and 93/68/EEC.
Properties
¹) For the critical applications
we advise for consultation
The materials used in manufacture are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
Flame test to VDE 0482 part 266-2 / HD 405.3, BS 4066 Part 3 / EN 50266-2 / IEC 60332-3 (equivalent DIN VDE 0472 Part 804 test method C)
Self-extinguishing and flame retardant according to DIN VDE 0482 Part 265-2-1 / EN 50265-2-1 / IEC 60332-1 (equivalent DIN VDE 0472 Part 804 test method B)
Corrosiveness of combustion gases according to VDE 0482 Part 267 / EN 50267-2-2 / IEC 60754-2 (equivalent DIN VDE 0472 part 813)
Halogen-free according to VDE 0482 Part 267 / EN 50267-2-1 / IEC 60754-1 (equivalent DIN VDE 0472 Part 815)
Smoke density according to VDE 0482 Part 1034-1+2 / IEC 61034-1+2 / DIN EN 61034-1+2 / BS 7622 Part 1+2 (equivalent DIN VDE 0472 Part 816)
Note
G = with green-yellow grounding
Clean room qualification tested with
analog type. Please note "clean room
qualified" when ordering.
is the Exclusive Importer of HUMMEL products. We offer over 6,000 different Types and Sizes of RoHS Compliant Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands, Circular Connectors, Conduit System, Industrial Enclosures and Other Related Cable Management Products which are rated the best in the industry.