Three Approvals Control Cable, Copper Shielded, EMI Preferred Type
Technical
Data
Helukabel
Special PVC control cable with
oil resistant outer jacket to
DIN VDE 0281 part 13, HD 21.13
S1 and to UL Style 2587
Temperature Range Flexing
-5°C to +70°C
(+23°F to +158°F) HAR
-5°C to +90°C
(+23°F to +194°F) UL+CSA
Fixed Installation
-40°C
to +70°C
(-40°F to +158°F) HAR
-40°C to +90°C
(-40°F to +194°F) UL+CSA
Nominal
Voltage U0/U
300/500 V (HAR)
U 600 V (UL+CSA)
Oil resistant as per HD/EN 60811-2-1, UL 1581 part 50.182
PVC self-extinguishing and flame retardant
according to DIN VDE 0482-332-1-2, DIN EN 60332-1-2 / IEC 60332-1 (equivalent
DIN VDE 0472 part 804 test method B)
UL-VW 1
The materials used in manufacture are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
G = with green-yellow
grounding
x = without green-yellow grounding (OZ)
The following amendments
in the cable designation result from
the new DIN VDE 0281 part 13 / harmonized
in accordance with HD 21.13S1: NYSLYÖ-J
(new: H05VV5-F) and NYSLYCYÖ-J (new:
H05VVC4V5-K). SEV-approval is no longer
applicable as a result of the harmonization.
UL-CSA-HAR approved
cables are offered to many companies
exporting anywhere in the world,
primarily designed for exporters,
used in machine tools, control systems,
assembly lines and other industrial
equipment. These cable are used for
flexible use for medium mechanical
stresses with free movement without
tensile stress or forced movements
in dry, moist and wet rooms, but
not for open air. EMI =
Electromagnetic Interference
To optimize the EMI features we recommend
a large round contact of copper braiding
on both ends.
=
The product is conformed
with the EC Low-Voltage
Directive 73/23/EEC and
93/68/EEC.
is the Exclusive Importer of HUMMEL products. We offer over 6,000 different Types and Sizes of RoHS Compliant Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands, Circular Connectors, Conduit System, Industrial Enclosures and Other Related Cable Management Products which are rated the best in the industry.
Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands Threads: PG, NPT, Metric, BSPP Threads Materials: Nylon, Nickel Plated Brass, PVDF (for chemicals and extreme temperatures) & Stainless Steel,
NEMA 4x and 6 (IP68, IP 69K). Approvals: RoHS, Deca BDE, UR, UL, CE, CSA, VDE, German Lloyd, etc. UL f1 (UL 746C) - Suitable for outdoor use with respect to exposure to ultraviolet light, water exposure and immersion in accordance with UL 746C
Circular Connectors (M16, M23, RJ45, M27 and M40) Sizes: M16 Signal, M23 Signal & Power, M27 Signal, M40 Power, M12/16 Twintus Types: Twintus, RJ45 Industrial Ethernet, PoE Fast Ethernet, Push-Pull, Stainless Steel, Over Molded Cordsets, Standard/EMI Ready Configurations: Signal (3-28 pole) & Power (6 & 8 pole) Materials: Nickel Plated Brass, Stainless Steel and Aluminum Approvals: RoHS, Deca BDE, UR, UL, CSA, TÜV, etc.
Industrial Enclosures (Plastic & Metal) Materials: Polycarbonate, ABS (Acryl-Butadiene-Styrene), Aluminum, Steel/Stainless Steel and Polyester. Types: Gray or Transparent Lids, available with Hinges and Latches, Plain Walls or Knockouts. Approvals: RoHS, Deca BDE, UL, CSA, TUV and CE.
Modular, Expandable, UV and Impact Resistant, NEMA 4, 4x (IP 66/67). Solar Plus for Photovoltaic applications.
Our Enclosures can be equipped with Strain Relief Fittings, Circular Connectors or Conduit Fittings. Other customization options like cutting & drilling are also available.
Conduit System
High Pull-Out Resistance, Robust Performance, Long Life Expectancy, Fastest/ Easy installation, No Tools required!
Fittings: Push-In, Turn-to-Seal, Snapclic DUO (Nylon or Nickel Plated Brass), Double-Seal, Flange/Bulkhead
Conduit: Standard and Super Flex Corrugated Conduit Accessories: Snap-In Mounting Brackets. NEMA 4 (IP 54/65) Approvals: RoHS, Deca BDE, UR, German Lloyd, CE, etc.
Hazardous Location / Explosive Proof Cord Grips, Cable Glands
These fittings are labeled and approved to withstand the required needs of a combustible environment. Materials: Nylon, Nickel Plated Brass, PVDF (chemical resistant & extreme temperatures), Stainless Steel. Threads: NPT, Metric & PG. NEMA 4x (IP 67) and 6 (IP 68/69K)
Approvals: RoHS, Deca BDE, UL, CSA, VDE, CE, EEx e, ATEX, German Lloyd, IECEx,
Ex-d/Ex-e, Ex-i EXIOS - High-end Cable Glands for armored cables in hazardous areas including the latest IECEx and ATEX certifications, for use in Ex-e, Ex-d and Ex-tD areas
Thread Adapters, Enlargers, Reducers
Convert, Increase or Decrease your thread size with our newest product line of Adapters, Enlargers and Reducers. Threads: NPT, Metric and PG. Materials: Black or Gray Nylon, Nickel Plated Brass, Aluminum, Stainless Steel. Approvals: RoHS, Deca BDE, CE, EEe x, ATEX, etc.
Hazardous / Explosive proof versions available.