Installation Methods & Operating Conditions
Power Cables and Insulated Wires for Fixed Installation
Installation method type A1 • Single conductor cables in insulation tube in a thermally insulated wall.
Installation method A2
•
Multi conductor cables or multi conductor plastic jacket cables in the insulation tube in a thermally insulated wall, whereby the walls for the methods of installation employed comprise an outer
weatherproof board, thermal insulation and an inner board of wood or materials similar to wood, having a temperature lag of 0,1 m2 x K/W. The plastic or metal insulation tube is mounted such that this is very
close to the inner wall without actually being in conduct with the wall.
Installation method B1 • Single conductor cables in insulation tube on a wooden wall.
Installation method B2
•
Multi conductor cables or multi conductor plastic jacket cables in insulation tube on a wooden wall.
For both installation methods, the insulation tube must be secured such that the space between conduit and the wall surface is less than 0.3 times the diameter of the insulation tube. The plastic or metal
insulation tube can be installed directly on the masonry construction or plastered surface, whereby the current carrying capacity of the cables or wires can then be higher. This problem is still being
investigated by CENELEC.
Installation method C
•
Single conductor or multi conductor cables, or single conductor or multi conductor plastic jacket cables, on a wooden wall.
The cables or insulated wires shall be mounted such that the space from the wall surface is less than 0.3 times the outer diameter of the cable or insulated wire. The current carrying capacity can be
increased when installed directly on or in the masonry construction as well as underneath the plaster. This problem is still being investigated by CENELEC.
Installation methods E, F and G
•
Single conductor or multi conductor cables, or single conductor or multi conductor plastic jacket cables, installed in the open air
The cable or insulated wire shall be installed such that the dissipation of heat is not impeded, whereby allowance shall be made for heating by other sources and for irradiation by sunshine. Natural
convection shall not be obstructed. The space from the cable or insulated wire by each bordering surface shall be 0.3 times that of the outside diameter. A space equal to that of the outside diameter is
sufficient for single conductor cables and plastic jacket wires in order to meet the current carrying requirements for an installation in the open-air.