Power and control cable,
PVC insulation and lead inner-jacket
to DIN VDE 0265
Temperature Range Flexing
-5°C to +70°C (+23°F to +158°F)
Fixed Installation
-30°C to +70°C (-22°F to +158°F)
Temperature at Conductor +70°C/+158°F Short Circuit Temperature +160°C/+320°F
(Short circuit duration 5 sec.)
Nominal Voltage U0/U
0.6/1 kV Nominal
Voltage U
for three-phase system 1.0
kV
for one-phase system 1.2 kV
(outer conductor insulated)
for one phase system 0.6 kV
(one outer conductor grounded) Nominal Voltage U0 = between
conductor and lead jacket
U = voltage between the outer
conductors, e. g. U0/U for
cables:
For three-phase system
For one-phase d.c. system,
U0 = U 1/2
(both outer conductor insulated)
For one-phase and d.c. system
U0 = U
(one outer conductor grounded)
Operating Voltage the voltage between
the conductors of a current-circuit
(or between conductor and
ground) in a given time
during undisturbed operation
under specified condition
Test Voltage (5
min.) 6.0 kV
Min. permissible Bending Radius approx. 12x cable Ø
Power Ratings
Table See Technical
Information
Code-Designation for
Power Cables with PVC or XLPE Insulation
Design
Identification
of Design
Explanations
Conductor
N
According
to VDE Standard
(No abbreviation for copper conductor)
A
Aluminum conductors
Y
Insulation of thermoplastic
Polyvinyl chloride (PVC)
2X
Insulation cross-linked
Polyethylene (XLPE)
Concentric
Conductor, Shielding
C
Concentric
conductors of copper wires and copper tape,
helically wounded
CW
Concentric conductors
of copper wires in wave conal formation
and and copper tape, helically wounded
CE
Concentric conductors
of copper wires and copper tape over each
individual conductor, helically wounded
Shielding
S
Shielding of copper wires
and copper tape, helically wounded
SE
Shielding of copper wires
and copper tape over each individual conductor,
helically wounded
(F)
Longitudinally water-proof
shielding
Armor
B
Armor of steel tape
F
Armor of galvanized flat
steel wires
G
Counter helix of galvanized
steel tape
Jacket
K
Lead jacket
Outer
Jacket
Y
PVC jacket
2Y
PE jacket
Cable
for U0/U 0.6/1 kV are
additionally designated with
-J
Cables with green-yellow
(green-natural) conductor are marked with
protective conductor
-O
Cables without green-yellow
(green-natural) conductor are marked without
protective conductor
Approvals
Cable
Construction
Bare copper conductor to DIN VDE
0295, BS 6360, IEC 60228 and HD 383
Conductor insulation of PVC, compound
type DIV4 to VDE 0276 part 603
Conductor identification to DIN VDE
0293-308
up to 5 conductors colored
7 conductors black with numbering
Green-yellow ground conductor
Conductors stranded concentrically
Overall jacket of soft plastics material,
if exists, permits also as extrusion
or taping or a combination of both
Lead inner-jacket, jointless and
enclosed
PVC outer jacket black, DMV5 to DIN
VDE 0276 part 603
Jacket color: Black
Application
These
cables of PVC insulation and
lead inner-jacket are installed
everywhere, where the danger
of chemical reaction of solvents,
energy fuels, oils, gasoline
or of that kind in filling
stations particularly in petrol
pump areas for carburetor propellants,
in refining plants and in chemical
industries are to be caused.
Suitable for installation under
ground, in water, indoor areas
and cable conduits.
=
The product
is conformed
with
the EC
Low-Voltage
Directive
2006/95/EG.
Properties
Advantage Good coupling resistance
due to enclosed lead jacket is suitable
for special EMI requirements (Electromagnetic
Interference)
The lead jacket is not permitted
to use as neutral-conductor (N)
If drain-wire exists, only for use
as grounding of lead jacket in a grounding
system e.g. in hazardous areas to DIN
VDE 0165. This drain-wire is not allowed
to install as protective, neutral or
ground conductor
Note
AWG sizes are approximate equivalent
values. The actual cross-section
is in mm�.
re = round solid
conductor sm =
sectional conductor
is the Exclusive Importer of HUMMEL products. We offer over 6,000 different Types and Sizes of RoHS Compliant Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands, Circular Connectors, Conduit System, Industrial Enclosures and Other Related Cable Management Products which are rated the best in the industry.
7374 S. Eagle Street
Centennial, CO 80112-4221 USA
Toll Free: 800-456-9012 / 303-699-1135 FAX: 303-680-5344