Description & No.
of conductors x cross-section in mm2
Outer
Diameter
mm
Copper Weight
kg/km
Weight
ca. kg/km
AWG
53032
NHXCH-FE
180/E 90 3X1.5 / 1.5 RE
16.9
66.0
380.0
16
53033
NHXCH-FE 180/E 90
3X2.5 / 2.5 RE
18.0
104.0
430.0
14
53034
NHXCH-FE 180/E 90
3X4 / 4 RE
19.0
161.0
530.0
12
53035
NHXCH-FE 180/E 90
3X6 / 6 RE
20.1
240.0
640.0
10
53036
NHXCH-FE 180/E 90
3X10 / 10 RE
22.0
408.0
850.0
8
53037
NHXCH-FE 180/E 90
3X16 / 16 RM
24.0
643.0
1150.0
6
53038
NHXCH-FE 180/E 90
3X25 / 16 RM
28.0
902.0
1700.0
4
53039
NHXCH-FE 180/E 90
3X35 / 16 RM
30.0
1190.0
2150.0
2
53040
NHXCH-FE 180/E 90
3X50 / 25 RM
34.0
1723.0
2800.0
1
53041
NHXCH-FE 180/E 90
3X70 / 35 RM
38.0
2410.0
3800.0
2/0
53042
NHXCH-FE 180/E 90
3X95 / 50 RM
44.0
3296.0
5100.0
3/0
53043
NHXCH-FE 180/E 90
3X120 / 70 RM
47.0
4236.0
6250.0
4/0
53044
NHXCH-FE 180/E 90
3X150 / 70 RM
51.0
4992.0
6900.0
300
kcmil
53045
NHXCH-FE 180/E 90
3X185 / 95 RM
56.0
6383.0
8550.0
350
kcmil
53046
NHXCH-FE 180/E 90
3X240 / 120 RM
65.0
8242.0
11150.0
500
kcmil
53047
NHXCH-FE 180/E
90 4X1.5 / 1.5 RE
18.0
81.0
435.0
16
53048
NHXCH-FE 180/E 90
4X2.5 / 2.5 RE
18.9
128.0
500.0
14
53049
NHXCH-FE 180/E 90
4X4 / 4 RE
20.0
200.0
610.0
12
53050
NHXCH-FE 180/E 90
4X6 / 6 RE
21.0
297.0
740.0
10
53051
NHXCH-FE 180/E 90
4X10 / 10 RE
23.0
504.0
1050.0
8
53052
NHXCH-FE 180/E 90
4X16 / 16 RM
25.0
796.0
1350.0
6
53053
NHXCH-FE 180/E 90
4X25 / 16 RM
30.0
1142.0
1950.0
4
53054
NHXCH-FE 180/E 90
4X35 / 16 RM
33.0
1526.0
2400.0
2
53055
NHXCH-FE 180/E 90
4X50 / 25 RM
37.0
2203.0
3200.0
1
53056
NHXCH-FE 180/E 90
4X70 / 35 RM
42.0
3082.0
4300.0
2/0
53057
NHXCH-FE 180/E 90
4X95 / 50 RM/
47.0
4208.0
5750.0
3/0
53058
NHXCH-FE 180/E 90
4X120 / 70 RM
51.0
5388.0
7100.0
4/0
53059
NHXCH-FE 180/E 90
4X150 / 70 RM
56.0
6540.0
8550.0
300
kcmil
53060
NHXCH-FE 180/E 90
4X185 / 95 RM
68.0
8159.0
10700.0
350
kcmil
53061
NHXCH-FE 180/E 90
4X240 / 120 RM
70.0
10546.0
13930.0
500
kcmil
Part-No.
Description & No.
of conductors x cross-section in mm2
Outer
Diameter
mm
Copper Weight
kg/km
Weight
ca. kg/km
AWG
53062
NHXCH-FE 180/E 90
7X1.5 / 2.5 RE
21.0
133.0
680.0
16
53066
NHXCH-FE 180/E 90
7X2.5 / 2.5 RE
21.0
200.0
680.0
14
53063
NHXCH-FE 180/E 90
12X1.5 / 2.5 RE
27.0
205.0
1050.0
16
53067
NHXCH-FE 180/E 90
12X2.5 / 4 RE
28.0
334.0
1050.0
14
53064
NHXCH-FE 180/E 90
24X1.5 / 6 RE
37.0
413.0
1900.0
16
53068
NHXCH-FE 180/E 90
24X2.5 / 10 RE
37.5
696.0
1900.0
14
53065
NHXCH-FE 180/E 90
30X1.5 / 6 RE
39.0
499.0
2200.0
16
53069
NHXCH-FE 180/E 90
30X2.5 / 10 RE
39.5
840.0
2200.0
14
Technical
Data
Halogen-free security cable
with improved characteristics
in the case of fire to DIN VDE
0266
Insulation Integrity 180 minutes to DIN VDE
0472 part 814
Functionality 90 minutes to DIN VDE
4102 part 12
Temperature Range
-30°C to +70°C (-22°F to +158°F)
Permissible Operating
Temperature at conductor +90°C/+194°F
Nominal Voltage U0/U
0.6/1 kV
Test Voltage 4000
V
Minimum Bending Radius Approx. 12x cable Ø
Radiation Resistance Up to 200x106 cJ/kg
(up to 200 Mrad)
Caloric Load Values See Technical Information
Approvals
FRNC
Cable
Construction
Bare copper conductor, solid
or stranded, to DIN VDE 0295
cl. 1 and cl. 2, BS 6360 cl.
1 or 2, IEC 60228 cl. 1 or cl.
2, HD 383
Double conductor insulation of mica
tape and cross-linked polymer
HI1, to DIN VDE 0207 part 23
Each single conductor covering with
flame resistant glass-fiber tape
Color coding of conductors according
to DIN VDE 0293-308
Conductors stranded in layer
Conductor wire shielding with helix
of copper tape
Bare copper wire shielding
with helix of copper tape
Outer jacket: Orange, polyolefin
compound HM4, to DIN VDE 0207
part 24
LS0H = Low Smoke
Zero Halogen-Free
Tests
Flame test to VDE 0482 part 266-2, BS 4066 part 3 / DIN EN 50266-2 / IEC 60332-3 (equivalent DIN VDE 0472 part 804 test method C)
Corrosiveness of combustion gases according to VDE 0482 part 267 / DIN EN 50267-2-2 / IEC 60754-2 (equivalent DIN VDE 0472 part 813)
Halogen-free according to VDE 0482
part 267 / DIN EN 50267-2-1 / IEC 60754-1 (equivalent
DIN VDE 0472 part 815)
Smoke density according to VDE 0482 part 1034-1+2 / IEC 61034-1+2 / DIN EN 61034-1+2 / BS 7622 part 1+2 (equivalent DIN VDE 0472 part 816)
Insulation integrity under flame propagation
to VDE 0472 part 814 IEC 60331
Burning behavior in fire (functionality)
of the complete cable system to DIN 4102
part 12 (90 minutes)
Application
Every place
where in case of fire human life
and material assets are to be protected
and safety consciousness take a
special significance, e.g. in industrial
complexes, power stations, communal
establishment, hotels, airports,
underground railway networks, hospitals
and outpatients clinic (DIN VDE
0107), department stores, data
processing centers, theaters, cinemas,
in multi-story buildings, public
gatherings, schools etc. (DIN VDE
0108), mining works, offshore plants,
leading centers, traffic communication,
emergency power supply and alarm
systems. Suitable for fixed installation
in dry and moist rooms, in, above,
on and beneath plaster as well
as in walls and in concrete.
These cables are suitable for outdoor
applications and in underground
by using in conduits or tubes.
Additionally valid also DIN VDE 0298
part 1 and 2. For the installation
in conduit all precautions must be
taken that no accumulation of water
can occur in the pipes.
=
The product is conformed with the
EC Low-Voltage Directive 2006/95/EG.
Properties
Halogen-free; no evolution
of corrosive and toxic gases
Flame retardant
Hardly flammable
Self-extinguished and fire
resistant
No flame propagation, therefore
security from fire
Low smoke density, no darkening
of emergency exits without
hindering the fire extinguishing
works
Toxicologically harmless
No self-ignition
Maintenance of functionality
during the increased current
load
FE 180: Insulation
integrity for
180 minutes. Tests to DIN
VDE 0472 part 814 IEC 60331. Insulation integrity under
direct flame propagation
for the test period of
180 minutes.
E 90: Functionality of
electrical cable systems
for minimum 90 minutes. Test
method to DIN 4102 part 12.
This fulfils the demands
of technical guide lines
for fire protection (supplement
1 to DIN VDE 0108 part 1).
The functionality for
90 minutes assures the functional
performance of water-pressure-rising
stations for the supply to
avoid smoke and heat in safety-stairs
and inner rooms, ladder shafts
and engine rooms for fire
brigade lifts, emergency
lifts for sickbeds in hospitals
and the fire brigade lifts.
Note
RE = round conductor, multiple-wire
RM = round conductor, single-wire
is the Exclusive Importer of HUMMEL products. We offer over 6,000 different Types and Sizes of RoHS Compliant Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands, Circular Connectors, Conduit System, Industrial Enclosures and Other Related Cable Management Products which are rated the best in the industry.
7374 S. Eagle Street
Centennial, CO 80112-4221 USA
Toll Free: 800-456-9012 / 303-699-1135 FAX: 303-680-5344