Description & No.
of conductors x cross-section in mm2
Outer
Diameter
mm
Copper Weight
kg/km
Weight
ca. kg/km
AWG
52771
N2XCH-FE 180/E 90
3X1.5 / 1.5 RE
16.5
66.0
330.0
16
52772
N2XCH-FE 180/E 90
3X2.5 / 2.5 RE
17.5
104.0
400.0
14
52773
N2XCH-FE 180/E 90
3X4 / 4 RE
18.5
161.0
480.0
12
52774
N2XCH-FE 180/E 90
3X6 / 6 RE
20.0
240.0
600.0
10
52775
N2XCH-FE 180/E 90
3X10 / 10 RM
22.0
408.0
840.0
8
52776
N2XCH-FE 180/E 90
3X16 / 16 RM
24.5
643.0
1130.0
6
52777
N2XCH-FE 180/E 90
3X25 / 16 RM
28.0
902.0
1560.0
4
52778
N2XCH-FE 180/E 90
3X35 / 16 RM
30.5
1190.0
1960.0
2
52779
N2XCH-FE 180/E 90
3X50 / 25 RM
34.0
1723.0
2610.0
1
52780
N2XCH-FE 180/E 90
3X70 / 35 RM
37.5
2410.0
3500.0
2/0
52781
N2XCH-FE 180/E 90
3X95 / 50 RM
43.0
3296.0
4700.0
3/0
52782
N2XCH-FE 180/E 90
3X120 / 70 RM
48.0
4236.0
5880.0
4/0
52783
N2XCH-FE 180/E 90
3X150 / 70 RM
52.0
4992.0
7300.0
300
kcmil
52784
N2XCH-FE 180/E 90
3X185 / 95 RM
57.5
6383.0
8760.0
350
kcmil
52785
N2XCH-FE 180/E 90
3X240 / 120 RM
63.5
8242.0
11280.0
500
kcmil
52786
N2XCH-FE 180/E 90
4X1.5 / 1.5 RE
17.5
81.0
390.0
16
52787
N2XCH-FE 180/E 90
4X2.5 / 2.5 RE
19.0
128.0
470.0
14
52788
N2XCH-FE 180/E 90
4X4 / 4 RE
20.0
200.0
570.0
12
52789
N2XCH-FE 180/E 90
4X6 / 6 RE
21.5
297.0
720.0
10
52790
N2XCH-FE 180/E 90
4X10 / 10 RM
24.0
504.0
1010.0
8
52791
N2XCH-FE 180/E 90
4X16 / 16 RM
26.5
796.0
1370.0
6
52792
N2XCH-FE 180/E 90
4X25 / 16 RM
30.5
1142.0
1940.0
4
52793
N2XCH-FE 180/E 90
4X35 / 16 RM
33.0
1526.0
2420.0
2
52794
N2XCH-FE 180/E 90
4X50 / 25 RM
37.5
2203.0
3240.0
1
52795
N2XCH-FE 180/E 90
4X70 / 35 RM
41.5
3082.0
4360.0
2/0
52796
N2XCH-FE 180/E 90
4X95 / 50 RM
47.5
4208.0
5900.0
3/0
52797
N2XCH-FE 180/E 90
4X120 / 70 RM
52.5
5388.0
7340.0
4/0
52798
N2XCH-FE 180/E 90
4X150 / 70 RM
57.5
6540.0
8840.0
300
kcmil
52799
N2XCH-FE 180/E 90
4X185 / 95 RM
63.5
8159.0
11020.0
350
kcmil
52800
N2XCH-FE 180/E 90
4X240 / 120 RM
70.0
10546.0
14140.0
500
kcmil
Part-No.
Description & No.
of conductors x cross-section in mm2
Outer
Diameter
mm
Copper Weight
kg/km
Weight
ca. kg/km
AWG
52801
N2XCH-FE 180/E 90
7X1.5 / 2.5 RE
20.5
133.0
520.0
16
52805
N2XCH-FE 180/E 90
7X2.5 / 2.5 RE
22.0
200.0
630.0
14
52802
N2XCH-FE 180/E 90
12X1.5 / 2.5 RE
26.0
205.0
770.0
16
52806
N2XCH-FE 180/E 90
12X2.5 / 4 RE
28.0
334.0
950.0
14
52803
N2XCH-FE 180/E 90
24X1.5 / 6 RE
35.0
413.0
1380.0
16
52807
N2XCH-FE 180/E 90
24X2.5 / 10 RE
37.5
696.0
1750.0
14
52804
N2XCH-FE 180/E 90
30X1.5 / 6 RE
37.0
499.0
1630.0
16
52808
N2XCH-FE 180/E 90
30X2.5 / 10 RE
39.5
840.0
2080.0
14
Technical
Data
Halogen-free security cable
with improved characteristics
in the case of fire to DIN VDE
0266
Insulation Integrity 180 minutes to DIN VDE
0472 part 814
Functionality 90 minutes to DIN VDE
4102 part 12
Temperature Range -30°C to +70°C (-22°F to +158°F)
Permissible Operating
Temperature at conductor +90°C
Nominal Voltage U0/U
0.6/1 kV
Test Voltage 4000
V
Minimum Bending Radius Approx. 12x cable Ø
Radiation Resistance Up to 200x106 cJ/kg
(up to 200 Mrad)
Caloric Load Values See Technical Information
Approvals
FRNC
Cable
Construction
Bare copper conductor, solid
or stranded, to DIN VDE 0295
cl. 1 and cl. 2, BS 6360 cl.
1 or 2, IEC 60228 cl. 1 or 2,
HD 383
Conductor with double insulation:
Flame retardant MICA-tape over
conductor
Conductor insulation with cross-linked
polyethylene, compound type 2XI1
to DIN VDE 0276 part 604
Conductors color coding to DIN
VDE 0293-308 and 0276 part 604
Concentric conductor of copper-bare
wires with helix of copper tape
Outer jacket of thermoplastic
halogen-free polyolefin, compound
type HM4 to DIN VDE 0276 part
604, flame retardant
Color: Orange
LS0H = Low Smoke
Zero Halogen-Free
Tests
Flame test to VDE 0482 part 266-2, BS 4066 part
3 / DIN EN 50266-2 / IEC 60332-3
(equivalent DIN VDE 0472
part 804 test method C)
Corrosiveness of combustion gases
according to VDE 0482 part
267 / DIN EN 50267-2-2 / IEC 60754-2
(equivalent DIN VDE 0472 part 813)
Halogen-free according to VDE
0482 part 267 / DIN EN 50267-2-1 / IEC
60754-1 (equivalent DIN VDE 0472
part 815)
Smoke density according to VDE 0482 part 1034-1+2 / IEC 61034-1+2 / DIN EN 61034-1+2 /
BS 7622 part 1+2 (equivalent DIN
VDE 0472 part 816)
Insulation integrity under flame
propagation to VDE 0472 part 814
cong; IEC 60331
Burning behavior in fire (functionality)
of the complete cable system to
DIN 4102 part 12 (90 minutes)
Application
Everywhere,
where in case of fire human life
and material assets are to be protected
and safety consciousness take a
special significance, e.g. in industrial
complexes, power stations, communal
establishment, hotels, airports,
underground railway networks, hospitals
and outpatients clinic (DIN VDE
0107), department stores, data
processing centers, theaters, cinemas,
in multi-story buildings, public
gatherings, schools etc. (DIN VDE
0108), mining works, offshore plants,
leading centers, traffic communication,
emergency power supply and alarm
systems. Suitable for fixed installation
in dry and moist rooms, in, above,
on and beneath plaster as well
as in walls and in concrete.
These cables are suitable for outdoor
applications and in underground
by using in conduits or tubes.
Additionally valid also DIN VDE 0298
part 1 and 2.
For the installation in conduit all
precautions must be taken that no
accumulation of water can occur in
the pipes.
=
The product is conformed with the
EC Low-Voltage Directive 2006/95/EG.
Properties
Halogen-free; no evolution
of corrosive and toxic gases
Flame retardant
Hardly flammable
Self-extinguished and fire
resistant
No flame propagation, therefore
security from fire
Low smoke density, no darkening
of emergency exits without
hindering the fire extinguishing
works
Toxicologically harmless
No self-ignition
Maintenance of functionality
during the increased current
load
FE 180: Insulation
integrity for 180
minutes. Tests to DIN VDE
0472 part 814 IEC 60331. Insulation integrity under
direct flame propagation
for the test period of 180
minutes.
E 90: Functionality of
electrical cable systems for
minimum 90 minutes. Test method
to DIN 4102 part 12. This fulfils
the demands of technical guide
lines for fire protection (supplement
1 to DIN VDE 0108 part 1).
The functionality for
90 minutes assures the functional
performance of water-pressure-rising
stations for the supply to
avoid smoke and heat in safety-stairs
and inner rooms, ladder shafts
and engine rooms for fire brigade
lifts, emergency lifts for
sickbeds in hospitals and the
fire brigade lifts.
Note
RM = round conductor, multiple-wire
RE = round conductor, single-wire
AWG sizes are approximate equivalent values. The actual cross-section is in mm2.
is the Exclusive Importer of HUMMEL products. We offer over 6,000 different Types and Sizes of RoHS Compliant Liquid Tight Strain Relief Fittings, Cord Grips, Cable Glands, Circular Connectors, Conduit System, Industrial Enclosures and Other Related Cable Management Products which are rated the best in the industry.