Operating temperature at conductor 70°C; Ambient temperature 30°C
Type Designation |
NYM, NYMZ, NYMT, NYIF, NYIFY, NHYRUZY, NYBUY, NYDY, N05VV-U, N05VV-R, NHXMH, NYY, NYCY 1) |
Installation:
- Direct
- Open Air |
Single - or Multi Conductor Cables on a wall
|
or |
|
|
Multi Conductor Cables with a space of min. 0.3 x diameter (d) to wall
|
Installation Method2) |
Direct Installation |
Installation in Open Air |
C |
E |
Number of Loaded Conductors |
2 |
3 |
2 |
3 |
Cross-section in mm² |
Current Ratings in Ampere (A) |
1.5 |
19.5 |
17.5 |
22 |
18.5 |
2.5 |
27 |
24 |
30 |
25 |
4 |
36 |
32 |
40 |
34 |
4 |
- |
33.022) |
- |
- |
6 |
46 |
41 |
51 |
43 |
10 |
63 |
57 |
70 |
60 |
10 |
- |
59.433) |
- |
- |
16 |
85 |
76 |
94 |
80 |
25 |
112 |
96 |
119 |
101 |
35 |
138 |
119 |
148 |
126 |
50 |
168 |
144 |
180 |
153 |
70 |
213 |
184 |
232 |
196 |
95 |
258 |
223 |
282 |
238 |
120 |
299 |
259 |
328 |
276 |
150 |
344 |
299 |
379 |
319 |
185 |
392 |
341 |
434 |
364 |
240 |
461 |
403 |
514 |
430 |
300 |
530 |
464 |
593 |
497 |
400 |
- |
- |
- |
- |
500 |
- |
- |
- |
- |
630 |
- |
- |
- |
- |
Type Designation |
NYY |
|
Single Conductor Cables with a space of min. 1 x Diameter (d) to wall |
Installation:
- Direct
- Open Air |
with contact |
with contact
|
with gap d
|
Installation Method2) |
Installation in Open Air |
Installation in Open Air |
F |
G |
Number of Loaded Conductors |
2 |
3 |
3 |
3 |
3 |
Cross-section in mm² |
Current Ratings in Ampere (A) |
1.5 |
- |
- |
- |
- |
- |
2.5 |
- |
- |
- |
- |
- |
4 |
- |
- |
- |
- |
- |
4 |
- |
- |
- |
- |
- |
6 |
- |
- |
- |
- |
- |
10 |
- |
- |
- |
- |
- |
10 |
- |
- |
- |
- |
- |
16 |
- |
- |
- |
- |
- |
25 |
131 |
114 |
110 |
146 |
130 |
35 |
162 |
143 |
137 |
181 |
162 |
50 |
196 |
174 |
167 |
219 |
197 |
70 |
251 |
225 |
216 |
281 |
254 |
95 |
304 |
275 |
264 |
341 |
311 |
120 |
352 |
321 |
308 |
396 |
362 |
150 |
406 |
372 |
356 |
456 |
419 |
185 |
463 |
427 |
409 |
521 |
480 |
240 |
546 |
507 |
485 |
615 |
569 |
300 |
629 |
587 |
561 |
709 |
659 |
400 |
754 |
689 |
656 |
852 |
795 |
500 |
868 |
789 |
749 |
982 |
920 |
630 |
1005 |
905 |
855 |
1138 |
1070 |
Conversion factors for deviating ambient temperature, grouping, installation under the ceiling, multi conductor cables and insulated wires - see DIN VDE 0298 part 4.
1) The current ratings are valid for cables with concentric conductor, only for multi conductor versions
2) For further installation methods – see DIN VDE 0298 part 4
3) See DIN VDE 0298 part 4
|